IDMT curve testing , REF620 relay Testing, OMICRON QUICK CMC TESTING ,Overcurrent Testing
full form of IDMT it’s inverse define minimum time
IDMT Curve formula they are
For normal inverse formula = TMS X 0.14 /Ir^0.02-1
For Very Inverse formula = TMS X 13.5/Ir-1
For extremely inverse formula = TMSX80/Ir^2-1
For Long Inverse formula = TMS X 120/Ir-1
On this formula TMS is time Multiple
Ir is fault current / normal current (or set current)
On this page of the site you can watch the video online IDMT curve testing | REF620 relay Testing | OMICRON QUICK CMC TESTING | Overcurrent Testing with a duration of hours minute second in good quality, which was uploaded by the user Barani Tech 31 July 2024, share the link with friends and acquaintances, this video has already been watched 1,271 times on youtube and it was liked by 51 viewers. Enjoy your viewing!